Inspectors and property managers see the same NFPA 25 findings over and over. If you own or manage a commercial building with a sprinkler system, knowing these in advance means fewer surprises, faster correction, and a smoother path to a clean report. These are the ten items most frequently cited on NFPA 25 inspection reports across the United States.

For Santa Fe commercial buildings: this guide applies to properties across Santa Fe · Santa Fe County · Northern NM. Resort hotels and historic buildings need insurance-grade NFPA 25 documentation. Enforcement is handled by Santa Fe Fire Department.

Last updated: 2026-11-08 · Published by Fire Solutions NW · NM Fire Protection License #400717 · Licensed in 6 states

1

Painted or Obstructed Sprinkler Heads

NFPA 25 §5.2.1.1.1

Sprinkler heads painted over during a tenant improvement, or blocked by stored goods within the 18-inch clearance, are the single most common finding. NFPA 25 §5.2.1.1.1 requires inspection of every head. If any part of the head is painted, loaded with corrosion/dust, or blocked, it must be replaced or cleared.

2

Pressure Gauges Past 5-Year Replacement

NFPA 25 §5.2.4.3

All pressure gauges on a sprinkler system must be replaced or recalibrated every 5 years. Gauges with illegible faces or stuck needles fail inspection. The sticker on each gauge must show a date within 5 years.

3

Missing or Illegible Hydraulic Nameplate

NFPA 25 §5.2.6

The hydraulic design nameplate must be permanently affixed to the system riser. If it is missing, corroded, or painted over, the inspection fails. Replacement requires engineered calculations.

4

Blocked Fire Department Connection (FDC)

NFPA 25 §13.7.1

Fire Department Connections must be unobstructed, clearly identified, and have intact caps. Overgrown landscaping, parked vehicles, and missing caps are common findings. Caps with internal threads damaged also cited.

5

Main Drain Test Pressure Drop Exceeding 10%

NFPA 25 §13.2.5

The annual main drain test must show residual pressure within 10% of the prior year's reading. A larger drop indicates water supply degradation and requires investigation — often a nearly closed valve or water main issue.

6

Control Valves Not Properly Sealed or Chained Open

NFPA 25 §13.3.2

All sprinkler control valves must be in the open position AND secured with a lock, seal, or electronic supervision. Missing seal or unsecured valves is a major finding — a closed valve is the #1 cause of system failure during an actual fire.

7

Antifreeze System Concentration Out of Spec

NFPA 25 §5.3.3

Antifreeze loops must be tested annually for proper concentration. Many legacy antifreeze systems use glycerin or propylene glycol that has been diluted over time. Concentration outside the listed range is an immediate correction.

8

Missing 5-Year Internal Pipe Inspection

NFPA 25 §14.2

Every sprinkler system requires a 5-year internal pipe inspection. Many owners are unaware and fail this item automatically on inspection #6. Dry-pipe systems in particular can show significant corrosion that only shows up during internal inspection.

9

Fire Pump Weekly / Monthly Test Records Missing

NFPA 25 §8.3

If the facility has a fire pump, the weekly (diesel) or monthly (electric) churn test records must be available on-site. Missing logs are cited even if the pump is in perfect condition. 2020 NFPA 25 changed electric pumps to monthly — verify your jurisdiction has adopted.

10

Dry Valve Trip Test Overdue or Trip Time Excessive

NFPA 25 §13.4.3

Dry-pipe valves require an annual partial trip test and full-flow trip test every 3 years. Trip times exceeding 60 seconds for schedule-system or exceeding design time for a hydraulically calculated system are findings. Often indicates air compressor issues or valve degradation.

Bottom line for Santa Fe facility managers

None of these are catastrophic on their own — but together they represent the baseline a well-run commercial facility keeps ahead of. Pre-inspecting against this list monthly, not just annually, is the lowest-cost way to maintain a clean NFPA 25 record.